CCGT cooling towers are thirsty. Two moves are cutting that bill fast
Water-Thirsty CCGT: Saving Thousands of Cubic Meters with High Cycles and Treated Wastewater
Cooling towers use a lot of water. Two moves cut that bill fast: run the towers at the highest cycles of concentration (COC) that still avoids scaling, and switch the makeup to treated wastewater. Field data show water savings of tens of percent and fast payback.
A combined-cycle gas turbine (CCGT) plant with a wet cooling tower uses large volumes of fresh water. Evaporation loss is usually 0.5–1.0 L/kWh (www.mdpi.com). One case is about 0.74 L/kWh. For a large plant that is about 2.8×10^6 m^3/year (www.mdpi.com).
Globally, industry is the largest water user, at about 45% of total abstraction. About 80% of that is for cooling (www.sciencedirect.com). Water scarcity is increasing. The IPCC estimates that about 50% of the population will experience water stress in 2025 (www.mdpi.com). Therefore CCGT operators are encouraged to shrink their water footprint.
For cooling towers the answer is clear. Run at the highest COC (cycles of concentration, the ratio of circulating water TDS to makeup) and use makeup sources that are not fresh water. DOE guidance says the goal of water efficiency is to "maximize COC" safely (www.energy.gov).
COC definition and operating limits
COC measures how intensively water is reused. The higher the COC, the lower the blowdown (discharge of some circulating water to limit salt accumulation) and the makeup. DOE notes that many towers operate at 2–4 COC. However, with adequate treatment "6 cycles or more may be possible" (www.energy.gov).
The water impact is real. Raising COC from 3 to 6 cuts makeup by ~20% and blowdown by ~50% (www.energy.gov). A target of "COC as high as possible" means just below the threshold for unacceptable scale or corrosion.
Scale, corrosion, and biofouling control
A higher COC raises TDS, Ca, Mg and silica, and the risk of scale precipitation. The common strategy is acid injection to lower pH and convert carbonate alkalinity to bicarbonate (allowing higher COC) (www.energy.gov), scale and corrosion inhibitors, and good makeup water quality.
Removing hardness with ion exchange opens the way to high COC without scale. With softened makeup, the scale threshold moves to a higher COC, if the chemical program is well managed. This practice usually starts with an ion-exchange-based softener and then a chemical program of scale inhibitors and corrosion inhibitors.
Without softening, acid and chemical consumption rises sharply. Automatic control of conductivity, the Langelier Saturation Index (LSI, an indicator of scale and corrosion potential), and side‑stream filtration help. An LSI near zero (slightly corrosive) indicates minimal deposit risk. To monitor conductivity, pH and blowdown alarms continuously, Sentinel CTS for cooling tower monitoring is available.
In practice, plants usually install 5–10 micron particle filtration with media such as sand silica dual media, then polish with a cartridge filter to control fouling. A dosing pump supports precise chemical dosing. In freshwater systems, blowdown conductivity is usually below ~4,500 µS/cm (www.sciencedirect.com).
The water benefit is large. Lowering hardness (Ca/Mg ions) with ion-exchange resin allows high COC without scale.
Direct water savings from high COC
DOE also estimates that doubling cycles from 3 to 6 cuts blowdown by ~50% (www.energy.gov).
Alternative makeup sources and reuse
Besides raising COC, non‑freshwater makeup cuts drinking water use. DOE guidance mentions air‑handler condensate, once‑through cooling drain, industrial rinse/process water, stormwater, and treated municipal/industrial wastewater, which matters most here (www.energy.gov). Good-quality municipal effluent is cited as suitable for makeup (www.energy.gov).
In practice, many power plants already use secondary or tertiary wastewater for cooling. This is common in dry regions such as the Southwestern US, Florida and the Middle East (www.powermag.com) (www.mdpi.com). Singapore's “NEWater” is an extreme example. It serves more than 5 million people, supplies industry and returns to the cooling system (www.mdpi.com). In Indonesia, reuse regulations exist but enforcement is weak. The country needs to adopt global best practices (www.mdpi.com).
For pre-treatment, membrane combinations such as ultrafiltration and brackish water RO are common in industrial reuse. Upstream, biological-membrane integration such as membrane bioreactors (MBR) produces reuse-quality water for cooling makeup.
TSE case: Aramco to US utilities
A Saudi Aramco pilot study tested TSE (treated sewage effluent, secondary-treated municipal wastewater) as makeup (www.watertechonline.com). TSE (TDS ≈1,500 mg/L, Ca ≈106 mg/L) has lower scaling potential (Langelier index ~0–0.5) than the previous groundwater (TDS ≈3,040 mg/L, Ca ≈233 mg/L). That groundwater caused severe condenser scaling at 2 COC (www.watertechonline.com).
Therefore the tower can run at 3.5 COC instead of 2.0. That cuts water demand by about 27% (www.watertechonline.com). In absolute terms, the 1,200-ton pilot saves about 16,500 m^3/year. If it is expanded to 5,000–6,000 tons of cooling, the potential is about 82,500 m^3/year, plus about 82,505 kWh of energy (www.watertechonline.com).
Pathogens were controlled. Legionella, coliform and viruses were not detected with continuous chlorination and biocide (www.watertechonline.com). Condenser surfaces stayed clean, with no mineral deposits. Therefore the study concluded that “TSE is a viable and sustainable alternative” as makeup (www.watertechonline.com) (www.watertechonline.com). A program like this needs a strong chemical package, such as biocides and scale inhibitors, including a dechlorination step when needed.
In the US, a 1,800 MW CCGT uses 100% secondary-treated municipal effluent (phosphate 13 ppm) as tower makeup (www.powermag.com). The plant switched to a specialized polymer treatment. This removed the need for side-stream lime softening, so it avoided CAPEX of $5–10 million. It also gave net O&M savings of ~$0.75–1.0 million/year (www.powermag.com) (www.powermag.com). Reclaimed wastewater needs careful management. Chloride, ammonia and organic levels trigger biofouling. High phosphate promotes calcium phosphate scale (www.powermag.com). With pre-treatment (filtration, dechlorination) and specialized chemistry, performance can be equal or better, without condenser scaling (www.powermag.com) (www.powermag.com).
Cooling tower blowdown recycling
Treating blowdown as a “water source” also works. Research shows that treated blowdown reuse (RO/UF/activated carbon) cuts system water consumption by ~13%. It also costs less than upgrading makeup (www.sciencedirect.com). This fits our industrial membrane systems packages. We select the element, for example membrane RO, from the blowdown characteristics.
One plant went further. A 750 MW CCGT in Chile ran a pilot with an RO–crystallizer system and reached 96% blowdown recovery (www.watertechonline.com). That is almost zero liquid discharge. COC can be pushed very high, limited by the inlet quality. The plant ran continuously for 30 days and recovered the CTBD stream that previously went to an evaporation pond (www.watertechonline.com) (www.watertechonline.com).
Cost, water tariffs, and ROI
Indonesian industrial water tariffs are the benchmark. For large users (for example Jababeka), the tariff is around US$0.60–0.80/m^3 (123dok.com). Jakarta’s domestic tariff for consumption >20 m^3 is about Rp5,550/m^3 (about $0.36) (megapolitan.kompas.com). Therefore industry pays more.
Every 1,000 m^3 saved is worth about $600–800, excluding sewer. A 500 MW CCGT uses about 3.7×10^6 m^3/year. If makeup drops by 20% (about 0.74×10^6 m^3), the saving is about $444–592 thousand/year. At $1/m^3 it becomes about $740 thousand/year. Savings on blowdown disposal and chemicals add value. The DOE says water savings must be compared with chemical costs. Acid adds labor and H₂SO₄ costs, and high COC can increase inhibitor requirements (www.energy.gov).
A typical package contains an ion exchange unit and cooling tower circuit protection chemicals.
In the Saudi pilot, chlorine at 1.5–2.5 mg/L kept health risk low at negligible additional chemical cost, because biocide was already dosed continuously (www.watertechonline.com). For reuse and blowdown treatment, the right membrane configuration determines OPEX and efficiency. A UF/RO module is one example. Flow, pressure and temperature monitoring of the UF/RO system can use Sentinel WT.
Aggregating benefits and hypothetical scenarios
Combining the methods doubles the benefits. With TSE plus higher COC, freshwater purchases for cooling approach zero. A hypothetical illustration: if a plant saves 1×10^6 m^3/year of drinking water, at $0.6/m^3 that is $600 thousand/year. If the project (piping + treatment) costs $2 million, payback is about 3–4 years. It is shorter if it includes blowdown disposal savings and incentives. Partial recycle (for example 50% blowdown) can also cut intake by more than half.
In short, high cycles and reuse cut freshwater intake and save money where water is scarce (www.sciencedirect.com) (www.powermag.com).