Inside the water kill chain: how food plants stack chlorination, UV, and ozone to hit drinking‑water safety

beta-pramesti-asiaindustry-food-and-beverageprocess-raw-water-treatment

Raw Water Disinfection at F&B Plants: Chlorine, UV, or Ozone? The Strategy Is Multi‑Barrier

Water in food and beverage plants is both a raw material and a cleaning agent. If it is not safe, products and public health are at risk. The three main disinfection technologies are chlorination, UV and ozone. Each has advantages and disadvantages. The key is a multi-barrier approach.

In the F&B industry, water affects taste, aroma, appearance, shelf life and product safety (water.co.id). Indonesian standards target drinking-water quality. That means zero E. coli/coliform in 100 mL, very low turbidity, and chemical thresholds including Trihalomethanes/THMs ≤100 µg/L according to WHO guidelines. The reference is Permenkes 492/2010 (www.kemkes.go.id). Raw water is rarely “perfect”. Therefore disinfection is a mandatory step.

No single method solves all problems at once. Chlorine is inexpensive and effective against bacteria/viruses. UV is reliable for chlorine-resistant pathogens such as Cryptosporidium. Ozone is powerful and also oxidizes organics. Their combination, the multi-barrier approach, gives ≥4–6 log reduction (logarithmic reduction, 1 log = 90%) against pathogens under variable source conditions (WHO Guidelines for Drinking-water Quality).

Before comparing technologies, physical pretreatment improves the chances of success in practice. This covers screening, coagulation, and media or membrane filtration. Membrane systems are usually used to filter particles and organics that interfere with downstream disinfection.

Chlorination spectrum and performance

Chlorination (gas, NaOCl/liquid, hypochlorite) is the standard for the water industry. “Chlorination is the standard against which others are compared” (www.ncbi.nlm.nih.gov). It works by oxidation of cell components. Under the right conditions, bacteria and many viruses can reach >3–5 log inactivation. CT (concentration×time, concentration×contact time) for 4‑log E. coli at pH ~7 is about 3–5 mg·min/L, for example 1–2 mg/L Cl₂ for 2–5 minutes (www.ncbi.nlm.nih.gov). In F&B practice, free residual is kept at ~0.2–0.5 mg/L to protect the distribution network.

The drawbacks are real. Chlorine forms disinfection by-products/DBPs such as THMs and haloacetic acids when it reacts with organic matter. WHO and the U.S. EPA limit total THMs to ~0.1 mg/L. Since the 1970s, the discovery of THMs has prompted “reexamination of available disinfection methodology” (www.ncbi.nlm.nih.gov). The pathogen spectrum is also limited. Cryptosporidium oocysts are essentially resistant. A CT of 3000–4000 mg·min/L achieves only 90% inactivation, and chlorine has been shown to be “largely ineffective against Cryptosporidium” (waterworld.com). Chlorine taste/odor is usually undesirable in beverages, and chlorite/chlorate formation occurs when chloramine or chlorine dioxide is used.

Chlorination is usually the cheapest per m³. Investment and energy are minimal. However, logistics remain: “two liters of 5% NaOCl must be stored per ML of water to dose 2–5 mg/L.” An academic review also concludes that chlorine is the “preferred option” because it is easy to use. However, other technologies (chloramines, ozone, UV) are used to reduce DBPs (researchgate.net). To control DBPs, pretreatment for organics is usually included before or after chlorination. For example, activated carbon media.

Keeping CT and residual correct needs dose control. Devices such as a dosing pump help keep the concentration stable without overshoot that triggers DBP formation. Continuous monitoring such as Betaqua Sentinel WS makes dose deviations visible quickly.

UV-C 254 nm: no chemicals and no DBPs

Ultraviolet (UV-C) damages microbial DNA/RNA. It is effective against bacteria, viruses, and protozoa. A dose of ~40 mJ/cm² usually gives ~3-log (99.9%) inactivation of Giardia cysts and Cryptosporidium oocysts (waterworld.com). Some adenoviruses/spores need up to ~100 mJ/cm² for 5-log. UV adds no chemicals or DBPs. It is common in the beverage/pharmaceutical industry (WHO GDWQ). Modern low‑pressure lamp life is ~9,000–12,000 hours. Maintenance intervals are predictable (enviroliteracy.org).

Its limitation is that it leaves no residual. Once water leaves the reactor, it can be recontaminated in pipes or storage. Therefore UV works best as a “final polish”, with an additional barrier if needed. UV also needs very clear water. Turbidity and particles can shield microbes. For that reason, pre-filtration or clarification is almost always needed, usually media filtration such as a sand/silica filter, for the UV system to work optimally.

Energy and O&M: low‑pressure installations use about 100–250 kWh per million gallons (MG). Medium‑pressure installations use about 460–560 kWh/MG (enviroliteracy.org). For comparison, chlorination systems use about 60–250 kWh/MG for pumping and mixing (enviroliteracy.org). Flow varies, so the UV reactor and its controls must keep the design dose at peak flow.

Ozonation: a strong oxidant, with no residual

Ozone (O₃) is generated on-site by corona discharge and injected into the water. It then breaks down quickly into O₂, so there is practically no long-term residual. Ozone oxidizes cell walls and organics. It sterilizes microbes quickly, reduces taste and odor compounds, and oxidizes Fe/Mn so they are easier to remove. For tough protozoa, the ozone CT requirement is much lower than the chlorine CT of ~3000–4000 mg·min/L, which gives only 90% Giardia/Crypto kill.

A typical dose of 1–5 mg/L with 5–10 minutes of contact can give multi-log kill of bacteria and high kill of viruses. The relative effectiveness does not change much at pH 6–8.5 and increases at warmer temperatures. Ozone produces far fewer halogenated DBPs than chlorine. It even reduces chlorine DBP precursors when it is placed upstream (WHO GDWQ).

Operational note: if there is no residual, you need an additional barrier against the risk of recontamination. You must monitor the dose closely. Excess ozone can form bromate if bromide is present, and bromate is a regulated parameter. Residual ozone must be quenched or off-gassed because it is toxic. Systems usually include an ozone destruct and monitor. Commercial generators use about 2–5 kWh/kg O₃. Ozone is usually more expensive per m³ than chlorination, depending on scale.

Complementary multi‑barrier design

No single disinfectant is best against all pathogens and conditions. Therefore a multi‑barrier approach is standard practice in F&B: a chain of physical, chemical and UV layers. If one step underperforms, the others still keep the quality.

The general scheme is screening → coagulation/clarification → media or membrane filtration → dual disinfection. Many facilities choose coarse pre‑screening, then media filtration or ultrafiltration (UF), then final disinfection (UV, ozone, or chlorine). One common example sequence: automatic screen 300 micron → inline coagulation → ultrafiltration membrane (absolute pore size 0.02–0.1 µm) → chlorine dosing. The UF stage gives a physical barrier with >6‑log capability for bacteria and protozoa. The chlorine residual downstream makes sure re‑growth is inactivated.

In chains that use coagulation and clarification, units such as a clarifier are usually used. "Coagulation" here usually uses a coagulant (example link: PAC) before filtration. For turbid river sources, the combination "coagulation/sedimentation → filtration → UV → chlorine" improves end‑to‑end quality assurance.

The effect is multiplicative. If filtration removes 2 log coliform and UV adds 3 log, the total is 5 log (99.999%). Another example, 3‑log UV for Crypto + 3‑log removal by filtration + 2‑log inactivation by chlorine gives ~8‑log total (99.999999%). That exceeds the ~4‑log Crypto removal usually needed.

This practice follows WHO guidelines and regulations (for example US EPA Long Term 2, Water Safety Plans). It also targets biofilm in pipes and storage that can protect Listeria and E. coli from routine cleaning. Biofilm is a microbial community embedded in a polymer matrix. It can release cells into the main stream and cause product contamination (digitaledition.food-safety.com). Continuous chlorine residual dosing, or periodic ozone or UV in the CIP loop, helps break up biofilm.

Practical scheme and outcome metrics

Example practical configuration: raw water → sand/carbon filter (reduce turbidity/organics) → UV reactor ~40–60 mJ/cm² → chlorine residual 0.2–0.5 mg/L. Here, filtration prevents “UV shadowing”, UV kills quickly, and chlorine protects during storage/distribution. Another alternative, ozone + chlorine: ozone oxidizes contaminants and inactivates >99.99% of microbes, then a small chlorine dose as residual. Pre‑ozonation also reduces chlorine DBP precursors.

When implemented correctly, multi‑barrier brings “potable water” quality into the plant. Parameters usually monitored afterward: total coliform = 0 CFU/100 mL, turbidity <0.1 NTU, THMs below the limit, and microbial challenge tests (spiked counts) that fall by several orders of magnitude. The global F&B trend adopts UV and ozone in multi‑barrier schemes for higher product purity and to avoid chlorine taste.

In Indonesia, compliance with Permenkes and SNI (zero pathogens, certain chemical limits) is usually achieved by a layered treatment train like this. Data-driven design uses CT tables, log-removal targets, and pilot testing. Engineers use these to size chlorinators, UV reactors, or ozone generators so that combined performance reaches the desired safety margin. The final risk target is a negligible waterborne infection rate, with a tolerable burden of disease <10^–6 DALY (disability-adjusted life years) per person-year according to WHO water safety goals (WHO GDWQ).

Source notes and reference figures

We cite these references for quality, energy and performance: NAS/UK standards and studies on chlorination and DBP (www.ncbi.nlm.nih.gov), UV dose for Crypto 40 mJ/cm² (waterworld.com), WHO drinking water guidelines (WHO GDWQ), U.S. EPA DBP limits (EPA NPDWR), biofilm and contamination (digitaledition.food-safety.com), and UV energy consumption and comparison with chlorination (enviroliteracy.org). The description of water's role in F&B refers to (water.co.id). Compliance with Permenkes refers to (www.kemkes.go.id).