Refinery Cooling Towers Run Hot and Dirty. This Is the Chemistry That Keeps Them Efficient.

beta-pramesti-asiaindustry-refineryprocess-cooling-water-dan-boiler-systems

Refinery Cooling Tower Chemical Program: A Coordinated Recipe That Maintains Efficiency Under Extreme Heat Load

In refinery cooling towers, a small increase in cycles-of-concentration (COC, the ratio of dissolved solids in circulating water to make-up) can save water on a large scale. However, hydrocarbon contaminants and high temperatures make it complicated. The answer is pH control, scale and corrosion inhibitors, and disciplined biocide use, all tied together by automation.

Refinery cooling towers handle very large recirculating flows, usually more than 90% of the plant's total make-up. Therefore every increase in COC gives real water and cost savings. However, refinery service exposes the system to high temperatures and traces of hydrocarbons and process chemicals (oil, process resin, amine, and others) that accumulate and settle easily. Many industry studies show that cooling water usually has a positive Langelier Saturation Index (LSI, a CaCO₃ saturation index for predicting scaling tendency). This means CaCO₃ supersaturation and a tendency to scale. Active microbes, including sulfate-reducing bacteria, form biofilm and corrosion products (www.scirp.org).

To keep heat-transfer efficiency and comply with effluent standards, the plant needs an integrated package: controlled blowdown, scale inhibitor and dispersant, corrosion inhibitor, and a strict biocide program. The instrumentation must keep dosing consistent and respond quickly to load changes.

pH Control and Measured Alkalinity

The bulk pH target is set in the mildly alkaline range, usually pH 7.5–8.5, to minimize corrosiveness without going over the scaling threshold. Industry references recommend neutral to slightly alkaline operation. The ideal range ≈7.0–9.0 is also cited as common practice (beta.co.id). Acid feed, for example sulfuric acid or HCl, neutralizes bicarbonate so carbonate does not precipitate. ASHRAE places acidifying + inhibitor/dispersant as the main scale-control strategy (handbook.ashrae.org).

In practice, we hold the saturation index around LSI 0 to +0.5. A negative LSI speeds up attack on steel. A strongly positive LSI means CaCO₃ scale that will form quickly. With pH adjustment and inhibitors, many systems can be held at LSI ≈ +0.2–+0.5. To keep the dosing accurate and stable, acid and chemical injection are controlled with precision dosing pumps such as dosing pump.

Scale Inhibitor and Dispersant

This program uses threshold-type scale inhibitors, usually organophosphonates and polyacrylate polymers. These interfere with nucleation and crystal growth. Phosphonates such as HEDP, PBTC, and ATMP adsorb onto incipient crystals and chelate calcium. For example, aminotrimethylene phosphonic acid (ATMP) has been shown to “raise” saturation tolerance by about +1.5 LSI units. In practice that multiplies the safe limits for calcium and alkalinity by up to three times. Modern programs tend to choose HEDP or PBTC over ATMP because they resist oxidizing biocides better.

Polyacrylate or polyacrylamide dispersants keep precipitated particles suspended. This is important when silica or phosphate is high, because these can form hard fouling films. Silica scale is very tenacious and a strong insulator. Therefore systems with silica >100–150 ppm may need a special silica inhibitor or higher bleed. In implementation, commercial inhibitor packages such as scale inhibitors are combined with dispersant chemicals to keep heat-exchange surfaces clean.

Blowdown and cycles of concentration strategy

Blowdown is measured by conductivity (or at fixed intervals). This partial water discharge, as outlined, is “essential to prevent scale formation and corrosion” (beta.co.id). A concentration of 4–6× (with bleed of 16–25% of circulation) is common for heavy-duty service. Without treatment, hardness and alkalinity limit COC to about ~3–4×. With a modern phosphonate/polymer program, 2–4× can be achieved reliably. Basic phosphonate/polymer treatment in hard water usually reaches only ~2–4× COC. A stronger program, for example softened make‑up plus specialty inhibitors, can push it to 6–10×.

Each increase in cycles has a financial impact. Doubling COC roughly halves blowdown. For example, raising COC from 3 to 6 cuts blowdown from ~33% to ~17% of flow and saves about 25–30% make‑up water. Routine testing keeps LSI in check and keeps hardness below ~400–500 ppm as CaCO₃ for a safe margin (beta.co.id). At many refineries, softened make‑up is used to push COC higher. This can be done with units such as a softener, or by selecting a suitable resin such as ion-exchange resin. This is consistent with the reported practice of “softened makeup plus specialty inhibitors.”

Film-forming corrosion inhibitors

The main material is carbon steel. Therefore film-forming inhibitors are used to build a passive layer. Common choices are organophosphonate, zinc salts (zinc), molybdate or silicate (handbook.ashrae.org). Toxic metal ions such as chromate are not used because of toxicity and regulation (handbook.ashrae.org). Zinc salts (a few mg/L) can coprecipitate to form a Zn-alloy protective film. Phosphonates complex iron and build a thin phosphate layer. Silicate or polyamines are also used for passivation. The key is consistent feed and control of water chemistry (handbook.ashrae.org). A good operating target is a very low corrosion rate (<<0.1 mm/year on steel). Practical formulations are available in lines such as corrosion inhibitors for cooling water.

Managing pH, dissolved oxygen, and materials

Corrosion is minimized with a near-neutral pH and reduced dissolved oxygen. Small doses of sodium nitrite or polyhydroxylamine are usually used together with film‑forming inhibitors to capture (scavenge) residual O₂. This also helps protect copper alloys if present. Note: closed circuits (for example, boiler condensate) need additional oxygen scavengers such as hydrazine or sulfite, as well as filming amines. For boiler oxygen scavengers, BETAGARD oxygen scavenger is available. Even open cooling loops benefit from low DO and neutral pH. Inhibitor selection needs to be matched to feedwater quality, system design, and operating parameters (beta.co.id).

Oxidizing and non‑oxidizing biocides

For bulk microbial control, we use strong oxidizers (chlorine, bromine, or chlorine dioxide). The scheme combines periodic shock and continuous feed. For shock (for example at startup or when biofilm is detected), ASHRAE recommends a dose of ~10 ppm free halogen to reach a residual of ~4–5 ppm for about 5 hours. This is a quick way to oxidize biofilm and organic fouling (handbook.ashrae.org). Afterward, a low residual is maintained. Guidance recommends free chlorine at ~0.2–0.5 ppm continuously (beta.co.id). At high organic load, chlorine dioxide can be selected. It is effective at 0.2–0.8 ppm and is not pH-sensitive, although it needs on-site production with sodium chlorite (handbook.ashrae.org). Commercial biocide formulations are widely available, including packages of biocides for cooling towers.

High hydrocarbon and COD levels can “consume” oxidizers. Therefore the program adds non‑oxidizing biocides such as glutaraldehyde, isothiazolin (for example DBNPA), or THPS. These can be continuous or intermittent, and they penetrate biofilm without relying on oxygen. Typical doses are in the single-digit ppm range. A common example is continuous glutaraldehyde at 5–10 ppm. Non-oxidizing agents are usually rotated to prevent microbial resistance.

Microbiological monitoring and tower hygiene

Biocide effectiveness is verified by routine microbiological testing. Without control, bacteria form biofilm that reduces heat transfer and accelerates corrosion (beta.co.id). Targets used: total aerobic bacteria <10^4 CFU/mL (CFU/mL, colony-forming units per milliliter, HPC/heterotrophic plate count) (beta.co.id). If counts rise, the program increases shock intensity or cleans the tower. Periodic drain‑and‑clean is still needed (beta.co.id). Operational support such as cooling tower cleaning service is usually part of the maintenance cycle.

Instrumentation, automation, and performance KPIs

Control ties all the components together. pH and conductivity sensors automate acid feed and bleed. An oxidation-reduction monitor tracks oxidant residual. Weekly laboratory or field tests (hardness, metal coupons, LSI, bacterial count) give feedback. A program like this usually raises the acceptable COC by 50–100% compared with untreated water. For example, moving from 4× to 6–8× (with the right chemistry) can cut blowdown by ~20–30%. This lowers make-up water a lot.

Meanwhile, the corrosion rate is suppressed to near zero (well below 0.1 mm/year) and heat-transfer surfaces stay clean for long campaigns. Targets such as iron release <10 ppm, copper release <1 ppm, and HPC <10^4 CFU/mL become achievable metrics.

Blowdown treatment and effluent compliance

Indonesian regulations such as Permen KLHK No. 5/2014 ask for low effluent strength. We collect the blowdown and treat it, for example with oil/water separation and pH neutralization. Therefore parameters such as oil & grease and BOD stay within the local discharge limits. For free oil separation we use an oil removal unit. For suspended solids and finer oil, dissolved air flotation such as DAF is an integrated option.

Data context and technical references

Industry studies and literature support the approach above. For example, an Aramco study shows produced water with LSI (>0) and high microbial content. This confirms the dual threat of scaling and biofouling (www.scirp.org). ASHRAE and water treatment handbooks describe acid + inhibitor strategies and specific biocide protocols (handbook.ashrae.org). Our field guidelines and engineering guidelines give realistic targets, for example hardness <500 ppm, pH ~7–9, free Cl 0.2–0.5 ppm and aerobic count <10^4 CFU/mL. These serve as daily control limits (beta.co.id).

Related product note: cooling water chemical formulations are available in cooling tower chemical. Complementary applications include the scale and corrosion inhibitors and biocide mentioned above.