Refinery Cooling Towers Face a Stealth Risk. ASHRAE 188 Shows How to Control It.

beta-pramesti-asiaindustry-refineryprocess-cooling-water-dan-boiler-systems

Refinery Cooling Towers Face a Stealth Risk. ASHRAE 188 Shows How to Control It.

Legionella grows well in the warm water with a lot of nutrients that refinery cooling towers usually hold. The towers can then put it into the air as aerosol. A written plan based on the standards keeps the risk low and production steady. The plan covers biocide control, cleaning and routine testing.

Industry: Refinery | Process: Cooling_Water_&_Boiler_Systems

Legionella pneumophila is the bacteria that causes Legionnaires' disease. It prefers water at 20–50 °C and it prefers stagnation. Many cooling systems have both conditions (pmc.ncbi.nlm.nih.gov). A tower without treatment can put Legionella into the air. Legionellosis is a severe pneumonia and about 10–15% of cases end in death (pmc.ncbi.nlm.nih.gov) (pmc.ncbi.nlm.nih.gov).

The risk is real. An outbreak at a hotel in 1976 caused more than 200 cases and 34 deaths. Reported cases in the US have quadrupled since 2000 (pmc.ncbi.nlm.nih.gov). The EU/EEA reached a record 10,700 cases (2.4 per 100k) in 2021 (www.ecdc.europa.eu). International standards (for example ASHRAE Standard 188) and the CDC/WHO guidelines put the emphasis on a full water management program (WMP).

In Indonesia, formal Legionella regulations are limited. However, the Ministry of Health lists legionellosis as an emerging threat. Best practice follows established WMP guidance (for example, CDC toolkit pages). In refining, this means chemistry, disinfection, mechanical hygiene and documentation are treated as important controls, not afterthoughts.

ASHRAE 188 water management program

An ASHRAE 188-aligned WMP (water management program) documents team roles, a full system schematic, hazard analysis, and control measures. It identifies the key risk factors for each tower: temperature, sediment and biofilm, water age, and disinfectant residual (pmc.ncbi.nlm.nih.gov) (www.cdc.gov). Routine environmental assessments map the piping, sumps, disinfectant feed points, drift eliminators (devices that reduce aerosol drift), and low-flow areas. They also note make-up water quality and process contaminants as nutrient sources.

Control strategies set measurable limits and verification actions. CDC emphasizes that scale, corrosion, and sediment controls (that is, cleaning) are important. Automated corrosion/scale inhibitors and coagulation are used to maintain clear water (www.cdc.gov). In practice this usually pairs a corrosion inhibitor and a scale inhibitor with dispersants. For example, a refinery may standardize on scale inhibitors for mineral control and corrosion inhibitors for metallurgy protection.

WMP verification usually includes continuous monitoring of parameters like pH (acidity/alkalinity), conductivity, and disinfectant residual, with automated sensors and logs. Automated feed equipment such as an accurate dosing pump and a documented cooling tower chemical program help keep residuals inside control limits.

Biocide dosing strategy and controls

A good biocide program is the main way to suppress Legionella. Cooling towers usually use oxidizing biocides (chlorine, bromine, chlorine dioxide, which release active oxidants) plus dispersants to limit biofilm. CDC recommends automated, continuous feed and monitoring to keep the target residuals (www.cdc.gov). Dosing is usually 24/7 to hold a steady residual of about 1–3 mg/L free chlorine. The chemical supplier sets the final setpoints. Non‑oxidizing biocides (for example isothiazolones, which disrupt cell functions without oxidation) can be rotated or added as supplemental slug treatments to penetrate biofilms. Refineries track chemical use and residuals against control limits. Automated controls help prevent under‑ or over‑dosing. A program like this is usually built on proven biocides and supported with dispersant chemicals.

During response disinfection or an outbreak, CDC advises circulating the water and adding an oxidizing biocide to reach ≥20 ppm free Cl₂, then holding it (usually 24 h) (www.cdc.gov). CDC also prescribes keeping residuals to maximize kill (for example ≥10 ppm Cl₂ for ≥24 h after the shock, and pH 7.8–8.5 for chlorine/bromine systems) (www.cdc.gov). The data is strong. Studies show shock plus continuous protocols reduce Legionella levels by >98% (pmc.ncbi.nlm.nih.gov). A European refinery tower with ~10⁵ CFU/L (colony‑forming units per liter) dropped to ~10² CFU/L after two 20 ppm chlorine shocks plus continuous chlorination (pmc.ncbi.nlm.nih.gov).

Cleaning and mechanical hygiene

Physical cleaning removes biofilms, sediments and scale that shield Legionella. CDC toolkits call for at least annual offline cleaning. The tower is removed from service, drained, the internals are scrubbed (fill media, basin, nozzles) and disinfected, then it goes back into operation (www.cdc.gov). Many facilities clean more often, semi-annually or quarterly, where contamination is high. Professional support such as a scheduled cooling tower cleaning service can standardize scope and documentation.

Chemistry and cleaning work together. Without cleaning, high oxidant levels can leave reservoirs of bacteria. One review found Legionella in 66.7% of municipal water storage‑tank sediments (www.ncbi.nlm.nih.gov). Therefore AWWA made tank draining and inspection mandatory at least every 3 years. If routine testing or any illness suggests proliferation, CDC prescribes a “shock and flush”: reach 20+ ppm sanitizer, circulate, then purge and neutralize before return to service (www.cdc.gov) (www.cdc.gov). Systems should not go back into service until disinfectant traces are absent and a satisfactory test is obtained.

Routine monitoring and testing

Continuous monitoring of tower function and water chemistry is the base of the WMP. Typical logs record pH, conductivity, corrosion inhibitor, scale inhibitor and biocide residual (daily or per shift). Drift eliminators and sumps are kept free of obstructions, and sensors are calibrated with documented maintenance.

Microbiological testing shows whether the program works. CDC notes that routine (periodic) sampling helps establish a baseline and “validate the water management program” (www.cdc.gov). For high‑risk sites (for example past cases or immunocompromised personnel), monthly or quarterly culture testing is prudent. Samples usually use 250 mL (milliliters) (www.cdc.gov) from basins and important recirculation points. Laboratory culture or PCR (polymerase chain reaction, a DNA method) guides actions. No universal safe level exists, but many jurisdictions trigger an investigation or disinfection around ~1,000 CFU/L. Exceedances prompt remedial cleaning and re‑treatment, followed by confirmatory testing.

Performance metrics and business impact

The results can be measured. Legionella counts stay low or are not detected, there are no outbreaks, and the plant meets its chemistry targets. Plants that use ASHRAE 188-style WMPs have reported a drop of about 80–100% in positive Legionella findings over a year, compared with systems without a WMP (case studies in industry reports). Regulators' reports in other countries show that tower inspections and disinfection compliance greatly reduce LD cases. Another example: a European manufacturer dropped Legionella from about 10⁵ CFU/L to <10² CFU/L after it tightened its biocide and cleaning schedule (pmc.ncbi.nlm.nih.gov).

A lapse has consequences. A 2015 outbreak in the US was traced to a neglected condo tower. An outbreak also costs money: health care, lawsuits, lost production. That cost can be tens to hundreds of times higher than a rigorous maintenance program. A strong plan combines tight biocide dosing, cleaning and testing with records. The outcome is health protection and economic savings. Recent guidance for healthcare and high‑risk facilities shows that sustained WMPs virtually eliminate legionellosis incidents (www.cdc.gov) (www.cdc.gov). The same standards apply in refinery cooling systems and also minimize risk. Legionella becomes a managed hazard instead of a disaster liability.

Some programs rely on chemistry. Then the feed and the monitoring need an accurate dosing pump to keep the residuals. The right cooling tower chemical package keeps the system within control limits, without over‑dosing or under‑dosing.

References and sources

References: Good sources from several countries support the practices above. For example, the CDC module Controlling Legionella in Cooling Towers lists scale and sediment control and automated disinfectant management as important (www.cdc.gov). It also says towers need offline cleaning every year (www.cdc.gov) (www.cdc.gov). A peer‑reviewed tower study found that shock chlorination plus continuous treatment gave a 98% reduction in Legionella counts (pmc.ncbi.nlm.nih.gov). International bodies note rising LD trends (for example EU/EEA 2021 data www.ecdc.europa.eu, US trends pmc.ncbi.nlm.nih.gov). These trends justify rigorous programs. Indonesian health authorities also list Legionella among emerging pathogens, so vigilance is needed (for example the FAQs on legionellosis on the Kemkes site).

Sources: CDC guidance (Cooling Towers Module, 2025, Routine Testing, 2025) (www.cdc.gov) (www.cdc.gov) (www.cdc.gov) (www.cdc.gov) (www.cdc.gov). Iervolino et al. 2017 (Int. J. Environ. Res. Public Health) (pmc.ncbi.nlm.nih.gov) (pmc.ncbi.nlm.nih.gov). MacIntyre et al. 2018 (Emerg. Microbes Infect.) (pmc.ncbi.nlm.nih.gov). ECDC 2023. NASEM 2019. etc.