Refineries Are Turning Towers Into Water Savers
Cooling Towers as a Water-Saving Arena: Drift Eliminators and High Cycles Make a Big Difference
In refineries, cooling towers can "drink" almost all the incoming water. Data shows that simple measures change the water-saving game. Maximize the cycles of concentration and install high-efficiency drift eliminators. This even opens the door to process-water reuse such as stripped sour water.
In many industrial facilities, up to 95% of the incoming raw water circulates through cooling towers. This makes the cooling tower a primary conservation target. In water-stressed regions such as Indonesia, rising costs and regulations are pushing refineries to cut their dependence on fresh water. The EPA's WaterSense guidance notes that raising cycles from 3 to 6 alone cuts makeup water by about 20% (EPA WaterSense).
The scale of this implementation is real. One study found that raising cycles from 6.5 to 9 would save more than 1.1×10^6 m³/year for the same cooling load (study of cycles of concentration and corrosion). Also, a simple upgrade to high-performance drift eliminators reduces "entrained droplets" (drift) to near-zero levels. This cuts wasted water and the treatment chemicals carried along with it.
Cooling tower water loss profile
The main water losses in cooling towers come from evaporation (about 1% of the flow for every 5.6 °C temperature drop), bleed/blowdown (discharging some water to control total dissolved solids/TDS), and, in smaller proportions, leaks and drift (droplets carried away by exhaust air). Without an eliminator, drift can be 0.05–0.2% of the circulating flow (EPA).
Blowdown increases as TDS rises. Therefore conservation strategies focus on two levers: reducing drift and maximizing cycles of concentration (COC, the ratio of dissolved salt concentration in the tower circulation to that in the makeup water).
High-efficiency drift eliminators
A drift eliminator captures droplets carried in the air stream and returns them to the collection basin. High-performance designs can cut drift to ≪0.005% of the circulation flow (EPA). In practice, modern models usually reduce drift by >90–99%. On a 200 m³/h tower, an old eliminator (0.002% drift) loses ~4 L/h. A high-eff model (0.0005% drift) loses only ~1 L/h. That difference adds up to about 26 m³/year per tower (Vistech Cooling).
This has knock-on effects. Less water and treatment chemical is lost. Less tower water is released, so the environmental footprint is smaller. It also helps emissions compliance, because regulators and Legionella safety guidelines limit drift. A good tower chemical program is a natural companion to this mechanical upgrade. One example is a cooling tower chemicals package (EPA, Vistech Cooling).
Operation at the highest cycles of concentration
The higher the COC, the lower the blowdown. Therefore makeup water consumption goes down directly. EPA calculates savings of ~17–20% when cycles are doubled. Going from 3 to 6 cuts makeup by about 20% (EPA WaterSense). The tower water balance (makeup = evaporation × COC/(COC − 1)) shows that raising COC from 2.2 to 10 lowers makeup by about 39% at the same cooling load.
With the right treatment, COC >10 is possible. The key is tight scaling control, because calcium and other ions precipitate when concentrated. Deposit inhibitors and pH control, for example through scale inhibitors, as well as softening based on an ion exchange softener, usually come as a package. Carbon steel corrosion is kept at a low rate.
Field example: raising COC from 6.5 to 9 (saving >1.1×10^6 m³/year) succeeded only after pH was lowered and a Zn/Mercaptobenzothiazole inhibitor was added to prevent calcium orthophosphate precipitation (study of concentration cycles and corrosion). In practice, we recommend stepwise monitoring of hardness, Langelier Saturation Index/LSI (an indicator of calcium carbonate scaling tendency), and online meters, for example Betaqua Sentinel CTS. With the right chemistry, COC can usually be doubled or more above baseline. A 20–40% reduction in blowdown can mean thousands of cubic meters of water saved per year for a large refinery. Precise dosing helps maintain the set point, for example using a dosing pump for acid/alkali or inhibitor.
Corrosion correlation must be maintained as COC increases. A corrosion inhibitors program compatible with the tower chemistry acts as a safety fence when salt concentration rises (EPA WaterSense).
Alternative water sources as makeup
To further reduce raw water use, refineries can use non‑potable sources as makeup: treated effluent (industrial/municipal), rainwater, condensate, and internal streams. Many “reclaimed water” sources such as municipal secondary effluent carry high hardness, alkalinity, phosphate, ammonia, or organics. This increases the risk of scaling and corrosion (www.powermag.com). However, the right treatment or a chemical program can address this.
A power plant study showed that municipal effluent with high phosphate (13 ppm PO₄) can still be run at high cycles if a “terpolymer” inhibitor is added. Therefore expensive softening or polishing is not needed (www.powermag.com). If a physical‑chemical route is chosen, side‑stream options such as reverse osmosis (RO) are also used to reduce the salt load.
Cooling tower blowdown recycling
Cooling tower blowdown can itself be recycled. A pilot test showed that blowdown reuse lowers the freshwater footprint by about 13% (www.sciencedirect.com). A case at a 750 MW power plant in Chile achieved 96% blowdown recovery by combining RO and a salt precipitation reactor. Conventional RO reaches about 55–60% (www.watertechonline.com). That means only 4% of the makeup needs fresh water. Therefore total use drops a lot. When blowdown is recycled into makeup, cycles can be pushed to the chemical limit, because discharge limits are no longer a factor (www.watertechonline.com, www.sciencedirect.com).
High-recovery RO operation needs tight scale control. Packages of membrane antiscalants are usually used to keep performance when salt concentration is high on the concentrate side.
Reuse of stripped sour water in refineries
Another internal opportunity is treated process water. At a refinery, sour water from crude distillation and hydrotreaters (water laden with H₂S/NH₃) usually goes to a stripper to remove acid gas. The result is called stripped sour water (SSW). Instead of being discharged, SSW can go to uses that do not need high quality. A study at Saudi Aramco's Ras Tanura refinery showed that SSW quality is good enough to replace boiler‑feed water in equipment “wash” duties (www.watertechonline.com).
Phased implementation (25%→50% replacement) has run stably and achieved ~33% SSW reuse, saving about US$1 million in the first year (www.watertechonline.com). Ras Tanura also plans to use the remaining SSW as cooling water (projected 50% reuse) once the supporting issues are addressed (www.watertechonline.com). Technically, this route needs characterization and simple pretreatment such as decantation, filtration, and ammonia control. For particulate polishing, the filtration scheme usually includes sand silica media or a cartridge filter.
Other non‑potable sources and disinfection
Other sources include rainwater, HVAC condensate and industrial effluent. All of them need particulate removal and biocide addition, because even when this water looks clean it is not sterile. ASHRAE notes that air-handler condensate is essentially distilled water. In humid climates it can meet about 10–40% of tower makeup demand (ASHRAE Handbook). Rainwater harvesting gives about 1 L per mm of rain per m² of roof (ASHRAE Handbook). When these alternative sources are blended into the tower circuit, a biocides program is needed to control microbial growth.
Measured results and implementation practice
This strategy package gives results you can audit. DOE/EPA guidance projects a 20%–60% reduction in tower makeup water when COC is raised to the 6–10 range (EPA WaterSense). Reliable drift eliminators reduce drift to negligible levels (EPA). Industrial cases support this. The cited refinery reuses about 33% SSW and saves about US$1 million/year (Ras Tanura refinery case study). A power plant demonstration cuts blowdown discharge by about 91% (96% reuse) (750 MW plant case study).
On the execution side, best practices include measuring all water flows, real-time conductivity and pH control, and a consistently run tower chemical program. Blending or switching water sources must account for differences in chemistry (for example LSI, silica, chloride) so hidden corrosion does not occur. In the right configuration, the financial return makes this step attractive: much less makeup water and lower operating costs. In many refineries, a scale inhibitor package, pH control, and membrane pretreatment such as membrane systems for reuse, backed by operational discipline, are enough to run aggressive COC without scaling. To design the package, see our cooling tower chemical program: scale and corrosion inhibitors, biocide, and dose monitoring to keep high COC safe.